Table 10. User Settings (continued)
Description
Battery Charging
Automatic Battery Tests
Full Power Battery Test
Number of Battery Strings
Battery Capacity
Battery Low Alarm Level
Set Nominal Output Voltage
Bypass Voltage High Limit
Bypass Voltage Low Limit
Nominal Output Frequency
Synchronization
Synchronization Window
Unsynchronized Transfer to Bypass
Output Frequency Slew Rate
Usage of Bypass
Transfer to Bypass When Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv Allowed/Disabled
X-Slot Signal Input Activation Delay
Input signal delayed shutdown delay
Site Wiring Fault Notice
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
Available Settings
ABM cycling/constant
Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled/Disabled
0 through 22
NOTE Options 3 through 22 are not used.
Option 2 optimizes battery recharging.
1 through 65535 watts per cell
1.750 through 1.950 volts per cell
Output: [120V/208V] [127V/220V]
NOTE The 127V/220V option is not used.
+1 through +20% (1% increments)
-1 through -20% (1% increments)
50 Hz or 60 Hz
Enabled/Disabled
±0.5 through ±3.0 Hz
(0.1 Hz increments)
Allowed/Not Allowed
0.1 though 5 hertz per second
(0.1 Hz increments)
Enabled/Disabled
After a delay/Immediately
-1 through 32767 seconds
(-1 means disabled)
Allowed/Disabled
0 through 65 seconds
1 through 65535 seconds
Enabled/Disabled
S
164201642 Rev C www.eaton.com/powerquality
OPERATION
Default Setting
ABM cycling
Enabled
Enabled
2 strings
34 W/cell
1.880 V/cell
120V/208V
120V +10%
120V -15%
60 Hz
Enabled
±2.0 Hz
Not Allowed
0.5 Hz/s
Enabled
After a delay
0s
Allowed
Allowed
5s
120s
Enabled
77