Eaton 9355-F47 Unirom User Manual page 102

10/15 kva
Table of Contents

Advertisement

SPECIFICATIONS
Table 13. Environmental and Safety Specifications
Operating Temperature
Transit Temperature
Storage Temperature
Ventilation
Altitude
Relative Humidity
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
96
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
50°F to 104°F (10°C to 40°C) Optimal battery performance: 77°F (25°C)
-13°F to 131°F (-25°C to 55°C)
32°F to 77°F (0°C to 25°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Front air intake, forced air, two fans, positive pressurization, temperature
9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
5–95% noncondensing
<56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
ANSI C62.41 Category B3
NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;
IEC 62040-2, FCC Part 15, ICES-003
S
164201642 Rev C www.eaton.com/powerquality
UPS-monitored
cULus