D9412GV3/D7412GV3/D7212GV3
How do I clear alarm memory?
Ensure all points are normal, and the enter your passcode and press [ESC], or press the
[Clear] soft key.
How do I determine if I have a ground fault?
On the control panel, measure voltage on terminal 9 (common) and terminal 10 (earth
ground). Approximately 6.5 to 6.8 VDC is normal voltage and equals no ground fault.
Disconnect wires until you see normal voltage to find your ground.
Can I add wireless capability to this control panel?
Yes. Use the Bosch Commercial Wireless Kit (ISW-CWKIT-01) and the proper Bosch
Commercial Wireless transmitters to fully integrate wireless on the control panel.
What type of cable do I use to connect my computer's COM port to a serial-enhanced direct
connection using the DX4010i?
A null modem cable is required.
How can I determine which points are not ready when my keypad reads "NOT READY TO
ARM"?
Press the NEXT key to scroll through faulted points. If the VIEW POINT STATUS menu item is
enabled, you can access it through the menu to determine the state of the faulted point.
What does it mean when my keypad reads "CHECK DEVICE"?
A point is faulted. The point is one that is configured to display as a device in the POINT INDEX
by marking YES for the DISPLAY AS DEVICE parameter.
I hear a trouble tone from my keypad but no point is shown as in trouble on the keypad.
How do I resolve this?
A point generates a trouble tone (buzz) when faulted if is configured to do so. To determine
which points are configured to buzz, look in the POINT INDEX for points with a non-zero value
for the BUZZ ON FAULT parameter.
How can I determine the meaning of an undefined signal received from central station?
Press 99 [ENTER] on the keypad to reveal the VIEW LOG menu item. Locate the signal in the
log by date and time.
Which reporting formats can the panel send?
Modem IIIa
What is the default Installer Code?
The code is 123.
What is the default User Code?
The code is 123456.
What is the default RPS Passcode?
The code is 999999.
Is the GV3 control panel keypad programmable?
Yes. RPS version 5.13 or later allows you to program all parameters of your GV3 control panel.
Keypad Programming, accessed with 99 [ENTER], allows you to program many parameters of
your GV3 control panel, for example, the RPS passcode. Refer to Section 3.4 RPS Programming
Using the Keypad Programming, page 10..
Where can I find free documentation and on-line support for this product?
Go to www.boschsecurity.us.
Bosch Security Systems, Inc.
2
or Contact ID. BFSK was replaced with Contact ID for the GV3 control panel.
Quick Reference Guide
Frequently Asked Questions | en
F01U170805 | 01 | 2010.11
25