8.3.5
MAXIMUM VALUE (3.4.2.)
Note
Read/write
Read only in PDM or AMS. Can be written via the handheld programmer.
Displays (in °C) the maximum temperature recorded by the internal electronics. The high and
low values are maintained over a power cycle.
Via SIMATIC PDM navigate to Maintenance and Diagnostics > Electronics Temperature.
8.3.6
INTERNAL TEMPERATURE (3.4.3.)
Read only. Displays (in °C) the current temperature on the circuit board recorded by the
internal electronics.
For access via SIMATIC PDM open the menu View – Process Variables and check the field
Electronics Temperature.
8.3.7
CONDENSED STATUS (3.5.)
When ENABLE (3.5.1.) (Page 115) is enabled, you can select the level of severity of errors,
and tailor a device response appropriate for your particular process.
● In EVENT INDEX (3.6.1.) (Page 116), you can select a particular event or error by means
of itsindex number.
● In EVENT STATUS (3.6.2.) (Page 117), you can assign a status to the selected event.
● In EVENT DIAGNOSIS (3.6.3.) (Page 118), you can assign a diagnosis to the selected
event.
8.3.7.1
ENABLE (3.5.1.)
Note
When cyclic communication is in progress, Condensed Status Mode cannot be changed.
Factory setting:
Setting range:
Description:
LR560 (PROFIBUS PA)
Operating Instructions, 06/2018, A5E34648471-AE
YES
NO
Disabled
YES
Enabled
Select Yes or No to enable/disable Condensed Mode.
Parameter Reference
8.3 DIAGNOSTICS (3.)
115