Parameter Reference
8.2 SETUP (2.)
8.2.3.3

LOE TIMER (2.3.3.)

Note
When a loss of echo occurs, VALUE (2.5.9.2.) (Page 111) determines the material level to
be reported when the fail-safe timer expires.
Factory setting:
Setting range:
Purpose:
8.2.3.4

TEMP UNITS (2.3.4.)

Factory setting:
Setting range:
Purpose:
8.2.3.5

CALIBRATION (2.3.5.)

LOW CALIBRATION POINT (2.3.5.1.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
HIGH CALIBRATION POINT (2.3.5.2.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
94
100 s
0.00 to 7200 seconds
Sets the reaction speed of the device to measurement changes.
Degrees C
Degrees C, F, R, or K
Selects the engineering unit to be displayed with the value representing
temperature.
40.000 m or 100.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNIT (2.3.1.) (Page 93) and displayed on the LCD and in PDM.
Any change to Low Calibration Point will cause the mA setpoints to be
updated.
UNIT (2.3.1.) (Page 93)
FAR RANGE (2.4.2.) (Page 98)
0.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNIT (2.3.1.) (Page 93)
When setting the High Calibration Point value, note that echoes are ignored
within NEAR RANGE (2.4.1.) (Page 98).
Any change to High Calibration Point will cause the mA setpoints to be
updated.
NEAR RANGE (2.4.1.) (Page 98)
UNIT (2.3.1.) (Page 93)
to Low Calibration Point. Units are
1)
to High Calibration Point. Units are
1)
LR560 (PROFIBUS PA)