Maintenance

7.2 Removing and inserting electronics modules during operation (hot swapping)

Death or severe personal injury could result if the following precautions are not taken
If a power supply is disconnected too early, sparking could cause an explosion.
After unlocking an ET 200iSP power supply, wait at least 2 minutes before disconnecting the
power supply in a hazardous atmosphere.
Permitted activities in zone 2
In addition to the activities permitted in zone 1, the following activity is also permitted:
Death or severe personal injury could result if the following precautions are not taken
Disconnection and connection of the cables for the 24 V DC Power Supply on the terminal
module TM-PS-A/ TM-PS-A UC or TM-PS-B/ TM-PS-B UC during operation. This activity is
permitted only when there is no risk of explosion or when there is no power applied at terminal
module TM-PS-A/ TM-PS-A UC or TM-PS-B/ TM-PS-B UC.
Disconnecting and connecting cables for the actuators at terminal module TM-RM/RM during
operation. This activity is permitted only when there is no explosion hazard or when there is
no voltage applied at terminal module TM-RM/RM.
See also
Inserting and labeling electronic modules 2 DO Relay UC60V/2A (Page 128)
7.2
Removing and inserting electronics modules during operation (hot
swapping)
Properties
● The ET 200iSP distributed I/O station supports the removal and insertion of one electronic
module (1 gap) during operation (RUN mode).
● If one electronic module is removed, the ET 200iSP remains in the RUN mode.
● If you remove more than one electronic module, this leads to an ET 200iSP station failure.
Once you have inserted all the electronic modules again, you must restart the ET 200iSP;
in other words, turn the power supply off and on at the power supply module PS.
186
WARNING
WARNING
Operating Instructions, 11/2017, A5E00247483-07