DSX-602 CableAnalyzer
Users Manual
Set the reference only after the testers are at an
ambient temperature between 10 °C and 40 °C
(50 °F and 104 °F).
The tester will not let you set the reference if the
patch cord is longer than 30 cm (12 in).
You can also set the reference with a 50 patch
cord
3
On the home screen, select a coaxial cable test.
4
On the home screen, tap TOOLS, then tap Set Reference.
5
On the SET REFERENCE screen tap TEST.
Coaxial adapter
with F connector
adapter
Figure 21. Reference Connections for Tests on Coaxial Cabling
54
Notes
DSX-CHA003
DSX-CHA003
COAX ADAPTER
COAX ADAPTER
30 cm (12 in) 75 
coaxial patch cord
Coaxial adapter
with F connector
adapter
BK179.EPS