PROGRAMMING EXHAUST FAN TIMER
INSTALLATION
1. Apply power (120, 208, or 240 VAC) to the A1 & A2 terminals.
Timer Wiring with Correct Wire Colors
Light Gray
Yellow
Dark Gray
Red/Yellow
Red
Yellow/Black
2. Hold down the SET and ADJ buttons for at least 3 seconds.
3. Repeatedly press the ADJ button until the letter E appears on the left-hand side.
4. Press the SET button.
5. Press the ADJ button until the letters M S appear.
6. Press the SET button.
7. Press the ADJ button to adjust the first digit to 2.
8. Press the SET button.
9. Press the ADJ button to adjust the second digit to 3.
10. Press the SET button.
11. Press the ADJ button to adjust the third digit to 0.
12. Press the SET button.
13. Press the ADJ button so there is an arrow facing downward.
14. Press the SET button.
13
07610-003-61-42-U