SPECIFICATIONS
NOTE: Typical Electrical Circuit is based on:
NOTICE
1. 125% of the full amperage load of the machine.
i
2. Typical fixed-trip circuit breaker sizes as listed in the NEC (Latest Edition).
Local codes may require more stringent protection than what is displayed here. Always verify with your electrical service
contractor that your circuit protection is adequate and meets all applicable national and local codes. Numbers in this manual
are for reference and may change without notice.
Volts
Phase
208
1
208
1
230
1
230
1
208
3
208
3
230
3
230
3
380
3
380*
3
415
3
415
3
440
3
440
3
208
1
208
1
230
1
230
1
208
3
208
3
230
3
230
3
460
3
460
3
* This model is wired in a wye configuration for the heaters.
07610-003-61-42-U
Rinse Heater
Hz
Rating
12 kW at 240 V
50
14 kW at 240 V
50
12 kW at 240 V
50
14 kW at 240 V
50
12 kW at 240 V
50
14 kW at 240 V
50
12 kW at 240 V
50
14 kW at 240 V
50
12 kW at 380 V
50
14 kW at 380 V
50
12 kW at 415 V
50
14 kW at 415 V
50
12 kW at 460 V
50
14 kW at 460 V
50
12 kW at 240 V
60
14 kW at 240 V
60
12 kW at 240 V
60
14 kW at 240 V
60
12 kW at 240 V
60
14 kW at 240 V
60
12 kW at 240 V
60
14 kW at 240 V
60
12 kW at 480 V
60
14 kW at 480 V
60
ELECTRICAL REQUIREMENTS
TempStar
Total Amps
71 A
78 A
78 A
86 A
45 A
49 A
48 A
53 A
29A
34A
26 A
29 A
21 A
25 A
69 A
76 A
76 A
84 A
43 A
47 A
46 A
51 A
22 A
25 A
Typical Electrical Circuit
90 A
100 A
100 A
110 A
60 A
70 A
60 A
70 A
40 A
45 A
35 A
40 A
30 A
35 A
90 A
100 A
100 A
110 A
60 AP
60 A
60 A
70 A
30 A
35 A
NOTICE
Imbalanced
wild leg goes
to L3.
NOTICE
Imbalanced
wild leg goes
to L3.
6