Note: For specific dimensional and weight information, refer to the unit submittals. The
Service Clearances
Figure 3. Service Clearance
Table 3.
Service clearances (inches)
Component
3
4
48
48
A (filter)
48
59
B (coil)
48
48
C (UV Lights)
D (external
61
61
starter or VFD)
D (internal
48
48
starter or VFD)
48
48
E (fan)
F (gas heat -
N/A
N/A
Ext Vestibule)
F (gas heat -
N/A
N/A
Int Vestibule)
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, hoods, pipe cabinets, etc. Sufficient clearance
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs,
or other high-voltage devices must be provided per NEC requirements.