Trane Performance Climate Changer Installation, Operation And Maintenance Manual page 42

Performance climate changer air handlers
Table of Contents

Advertisement

Installation - Mechanical
13. Install the section-to-section screws inserting the appropriate screws through the overlapping
Figure 26. Section-to-section seam cap installation
Seam cap
38
flanges using a powered impact gun and taking care not to strip the screws. Outdoor air
handlers will ship with a seam cap that is to be installed over the section-to-section seams.
Factory-supplied butyl tape must be applied over the seam prior to seam cap being applied. See
Figure
26.
See detail
Butyl tape