Air Filters; Throwaway Filters; Permanent Filters; Cartridge Or Bag Filters - Trane Performance Climate Changer Installation, Operation And Maintenance Manual

Performance climate changer air handlers
Table of Contents

Advertisement

Air Filters

Rotating Components!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/ tagout procedures to ensure the equipment cannot be inadvertently energized. Secure
drive sheaves to ensure rotor cannot freewheel. Failure to secure drive sheaves or disconnect
power before servicing could result in death or serious injury.
Refer to product catalog for filter sizes, types, and quantities.

Throwaway Filters

To replace throwaway filters, install new filters with the directional arrows pointing in the direction
of airflow.
Note: Bag and cartridge filters must have an airtight seal to prevent air bypass. If using filters not

Permanent Filters

To clean permanent filters:
1. Disconnect all electrical power to the unit.
2. Wash the filter under a stream of water to remove dirt and lint.
3. Remove oil from the filter with a wash of mild alkali solution.
4. Rinse the filter in clean, hot water and allow to dry.
5. Coat both sides of the filter by immersing or spraying it with Air Maze Filter Kote W or an
6. Allow to drain and dry for about 12 hours.
7. Reinstall the filter.
Note: It may be preferable to keep extra, clean filters to replace the dirty filters to minimize unit

Cartridge or Bag Filters

To replace cartridge or bag filters:
1. Disconnect all electrical power to the unit.
2. Remove the dirty filters from their installed position.
3. Keeping the new bag filters folded, slide each filter into the filter rack, pushing them tightly
Note: The pleats should be in the vertical position.
4. If using the optional pre-filters, replace them on the appropriate filter rack.
5. Close and secure the access door.

Drain Pans

Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
CLCH-SVX07C-EN
WARNING
supplied by Trane, apply foam gasketing to the vertical edges of the filter.
equivalent.
downtime for filter maintenance.
against the unit.
WARNING
Routine Maintenance
121