SECTION 3 - PRINTERS
YORK SetpOintS
ChilleR id 0
(c) 1997 - 2004 YORK INTERNATIONAL CORPORATION
Tue 20 Apr 2004
4:48:56 PM
Software Versions
-------------------------------------------------------
Controls
BIOS
Kernel
GUI
SIO
GPIC
Exp I/O
System Information
-------------------------------------------------------
System Language
Data Display Mode
Control Source
Remote Analog Input Range
Clock
Options
------------------------------------------------------
Prelube
Chilled Liquid Pump Operation
Refrigerant Selection
Power Failure Restart
Liquid Type
Flow Switch
Printer Setup
------------------------------------------------------
Automatic Printer Logging
Log Start Time
Output Interval
Printer Type
Baud
Data Bits
Parity
Stop Bits
COM 2 Setup
-------------------------------------------------------
Baud
Data Bits
Parity
Stop Bits
Evaporator
-------------------------------------------------------
TSP1 - Leaving Chilled Local Setpoint
Leaving Chilled ISN Setpoint
Leaving Chilled Modem Setpoint
Leaving Chilled Analog Setpoint
Leaving Chilled Digital Setpoint
TSP2 - Remote Range
Restart Offset
Restart Setpoint
Shutdown Offset
Shutdown Setpoint
Brine Low Evaporator Cutout
Smart Freeze
Refrigerant
Condenser
-------------------------------------------------------
High Pressure Warning Threshold
Drop Leg
Oil Sump
-------------------------------------------------------
Compressor Oil Pump Package
Speed
Standby Lube

figure 56 - SAMPLE PRINTOUT (SETPOINTS)

156
= C.E09.12.00.000.00.551
= C.OPT.00.01
= 1.19
= 0.35
= 1.23
= 0.05
= 0120204302003
= English
= English
= Local
= 0-10 Volts
= Enabled
= Standard
= Standard
= R134a
= Auto
= Water
= Analog
= Disabled
= 12:00 AM
=
60 Min
= Okidata
= 9600 Baud
= 8 Bits
= None
= 1 Bit
= 57600 Baud
= 8 Bits
= None
= 1 Bit
=
42.1 ~F
=
42.1 ~F
=
42.1 ~F
=
42.1 ~F
=
42.1 ~F
= 10.0 ~F
=
0.0 ~F
=
42.1 ~F
=
4.0 ~F
=
38.1 ~F
=
25.0 Psig
= Off
= Enabled
= 162.5 Psig
= Enabled
= Variable
= Enabled
Variable Speed Oil Pump
------------------------------------------------------
Pressure Setpoint
Control Period
Proximity Probe
----------------------------------------------------------
High Speed Thrust Bearing Proximity Reference =
Misc. Setpoints
----------------------------------------------------------
HGVRAT - Hot Gas Valve Ratio Bypass
HLSP2 - Hotwell High Level
LCVM - Subcooler Level Valve Minimum Position =
Configuration Setpoints
----------------------------------------------------------
MSP1 - High Head Minimum Speed
MSP2 - Low Head Minimum Speed
MSSP1 - Capacity Ratchet Mode HGV Reselection =
MSSP2 - Capacity Ratchet Mode PRV Reselection =
MSSP3 - Capacity Ratchet Mode SPD Reselection =
MSSP4 - Turbine Start Mode
MSSP6 - Turbine Lubrication Type
MSSP7 - Speed Control Mode
MSSP8 - Power Limiting Mode
MSSP10 - Hotwell Pump Mode
MSSP11 - Vacuum Pump Mode
MSSP13 - Turbine Shaft Vibration Sensors
MSSP14 - Turbine Bearing Temperature Sensors
MSSP15 - Turbine First Stage Pressure Sensor
MSSP16 - Turbine Nozzle Solenoids
MSSP17 - Turbine Stage Count
PRVM - PRV Minimum Open Position
MVP1 - High Head Minimum PRV
MVP2 - Low Head Minimum PRV
Pressure Setpoints
-------------------------------------------------------
PD1 - Maximum Pressure Differential
PD2 - Minimum Pressure Differential
PSP5 - Vacuum Pump Shutdown
PSP6 - Ready To Run Turbine Exhaust Pressure = 5.0 Psia
PSP7 - Turbine Exhaust Steam High Pressure
PSP8 - Turbine Supply Oil Low Pressure
PSP9 - Turbine Auxiliary Oil Pump Off
PSP10 - Turbine Auxiliary Oil Pump On
PSP12 - Open Ejector Steam Inlet
PSP13 - Turbine Nozzle Solenoid #1 Activate =
PSP14 - Turbine Nozzle Solenoid #2 Activate =
PSP15 - Turbine Nozzle Solenoid Deadband
Ramp Rate
-------------------------------------------------------
RRSP1 - Temp Control Setpoint Ramp Rate
RRSP2 - Hot Gas Valve Ramp Rate
RRSP3 - Slow Roll Speed Setpoint
RRSP4 - Minimum Rated Speed Setpoint
RRSP5 - Rated Speed Setpoint
RRSP6 - Soft Shutdown Speed Setpoint
RRSP7 - Main Steam Inlet Block Valve
RRSP8 - PRV Ramp Rate
RRSP9 - Slow Roll Steam Bypass Valve
RRSP10 - Subcooler Level Control Setpoint Ram =0.1 %/Sec
FORM 160.67-O1
ISSUE DATE: 4/1/2015
=
35 Psid
= 0.9 Sec
50 Mils
=
5 %
=
90.0 %
25 %
=
4500 RPM
=
3600 RPM
3 %
3 %
3 %
= Auto
= Pump
= Variable Speed
= Pressure
= Dual
= Dual
= Enabled
= Disabled
= Enabled
= Enabled
=
7
=
0 %
=
5 %
=
0 %
=
70.0 Psid
=
45.0 Psid
=
1.5 Psia
=
3.5 Psia
=
8.0 Psig
=
16.0 Psig
=
6.0 Psig
=
5.0 Psia
45.0 Psig
50.0 Psig
=
5.0 Psig
=
0.2 ~F/Sec
=
10.0 %/Sec
=
50 RPM
=
100 RPM
=
10 RPM
=
50 RPM
=
5 %/Sec
=
10.0 %/Sec
=
5 %/Sec