Figure 55 - Sample Printout (Status) - York YST Operation Manual

Steam turbine drive centrifugal liquid chiller with optiview control center design level f and g
Hide thumbs Also See for YST:
Table of Contents

Advertisement

SECTION 3 - PRINTERS
YORK Update
ChilleR id 0
(c) 1997 - 2004 YORK INTERNATIONAL CORPORATION
Tue 20 Apr 2004
4:46:25 PM
SYSTEM READY TO START
CONTROL PANEL - POWER FAILURE
Controls C.E09.12.00.000.00.551
Run Time
0 Days
0 Hr
Operating Hours
Number Of Starts
Control Source
Evaporator
-------------------------------------------------------
Leaving Chilled Active Setpoint
Chilled Liquid Pump Start Contact
Chilled Liquid Flow Switch
Leaving Chilled Liquid Temperature
Return Chilled Liquid Temperature
Evaporator Pressure
Evaporator Saturation Temperature
Evaporator Refrigerant Temperature
Small Temperature Difference
Condenser
-------------------------------------------------------
Condenser Liquid Pump Start Contact
Condenser Liquid Flow Switch
Leaving Condenser Liquid Temperature
Return Condenser Liquid Temperature
Condenser Pressure
Condenser Saturation Temperature
Small Temperature Difference
Drop Leg Refrigerant Temperature
Sub Cooling Temperature
Compressor
------------------------------------------------------
Discharge Temperature
Oil Sump
-------------------------------------------------------
Oil Pump Run Output
Sump Oil Pressure (LOP)
Pump Oil Pressure (HOP)
Oil Pressure
Oil Sump Temperature
Oil Heater Output
Oil Return Solenoid
Variable Speed Oil Pump
-------------------------------------------------------
Oil Pump Drive Command Frequency
Variable Speed Oil Pump Control Mode

figure 55 - SAMPLE PRINTOUT (STATUS)

154
0 Min
=
65 Hr
=
5
= Local
=
42.1 ~F
= Open
= Open
=
42.0 ~F
=
58.0 ~F
=
34.5 Psig
=
39.4 ~F
=
40.0 ~F
=
2.0 ~F
= Open
= Open
=
94.3 ~F
=
85.0 ~F
= 116.3 Psig
=
96.2 ~F
=
1.9 ~F
=
90.0 ~F
=
6.2 ~F
= 120.0 ~F
= Off
=
33.1 Psig
=
32.9 Psig
=
0.0 Psid
= 136.4 ~F
= On
= Off
=
25.0 Hz
= Auto
Proximity Probe
--------------------------------------------------------
High Speed Thrust Bearing Proximity Different =
Subcooler Level
-------------------------------------------------------
Subcooler Level Setpoint
Subcooler Level Pulldown Time Remaining
Subcooler Level
Control Output Signal
Subcooler Level Auto/Manual Mode
Hot Gas Bypass
-------------------------------------------------------
Hot Gas Ratio Calculation
Temp Setpoint
Hot Gas Temp Calculation
HGV Ramp
Control Output Signal
HGV Auto/Manual Mode
Pre-Rotation Vanes
--------------------------------------------------------
PRV Position
PRV Ramp
PRV Command
PRV Motor Switch
PRV Auto/Manual Mode
Speed Control
--------------------------------------------------------
Speed Setpoint
MSSP7 - Speed Control Mode
Turbine Speed
Control Output Signal
Turbine Rotation
Speed Setpoint Auto/Manual Mode
Capacity Control
--------------------------------------------------------
Capacity Ratchet Mode
Capacity Ratchet: HGV Drive
Capacity Ratchet: PRV Drive
Capacity Ratchet: SPD Drive
Anti-Surge Calculated Min. Speed
Anti-Surge Calculated Min. PRV
Temperature Controller: Selected Override
Override Limit
Temperature Controller: Control Percentage
Temperature Controller: Control Mode
Head Pressure
PD1 - Maximum Pressure Differential
PD2 - Minimum Pressure Differential
MVP1 - High Head Minimum PRV
MVP2 - Low Head Minimum PRV
MSP1 - High Head Minimum Speed
MSP2 - Low Head Minimum Speed
FORM 160.67-O1
ISSUE DATE: 4/1/2015
2 Mils
=
0 %
=
0 Sec
=
50 %
=
100 %
= Auto
=
100 %
=
40.9 ~F
=
0 %
=
100 %
=
100 %
= Auto
=
0 %
=
0 %
=
0 %
= Open
= Auto
=
0 RPM
= Variable Speed
=
0 RPM
=
0.0 %
= Open
= Auto
= Hot Gas
=
100 %
=
7 %
=
71.1 %
=
3200 RPM
=
7 %
= None
= 100.0 %
=
0.0 %
= Inactive
=
81.8 Psid
=
70.0 Psid
=
45.0 Psid
=
5 %
=
0 %
=
4500 RPM
=
3600 RPM
JOHNSON CONTROLS