Configuration Screen 2; Figure 38 - Configuration Screen 2 - York YST Operation Manual

Steam turbine drive centrifugal liquid chiller with optiview control center design level f and g
Hide thumbs Also See for YST:
Table of Contents

Advertisement

FORM 160.67-O1
ISSUE DATE: 4/1/2015
noTe: OptiView
Control Center Screens shown may NOT represent the exact screens according to the software version utilized.

figure 38 - ConfiguraTion SCreen 2

overvieW
This screen is used to configure the analog inputs
dedicated for the customer supplied steam and water flow
transmitters. These inputs must be configured to match
the full- scale range and the linearity of the transmitter
output signal in order for the data fields to display the
correct values. The transmitters must be connected to
the Control Center per the Field Control Modifications
Wiring Diagram YORK Form 160.67-PW2.
prograMMable
FSE1 – Steam Flow Sensor Enable
Screen: Steam System
Range: Enabled/Diasabled
This must be set to Enabled to display the rate of steam
flowing through the turbine.
FSE2 – Evaporator Flow Sensor Enable
Screen: Evaporator
Range: Enabled/Diasabled
This must be set to Enabled to display the rate of chilled
liquid flowing through the evaporator.
FSE3 – Condenser Flow Sensor Enable
Screen: Condenser
Range: Enabled/Diasabled
JOHNSON CONTROLS

ConfiguraTion SCreen 2

Default: Disabled
Default: Disabled
Default: Disabled
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
This must be set to Enabled to display the rate of
cooling liquid flowing through the condenser.
fSp1 – Steam flow Sensor range
Screen: Steam System
Range: 0-30,000 Lb/Hr
This is the calibrated upper range limit of the steam
flow transmitter output signal.
fSp2 – evaporator flow Sensor range
Screen: Evaporator
Range: 0-10,000 Gal/Min
This is the calibrated upper range limit of the chilled
liquid flow transmitter output signal.
fSp3 – Condenser flow Sensor range
Screen: Condenser
Range: 0-10,000 Gal/Min
This is the calibrated upper range limit of the condens-
er liquid flow transmitter output signal.
FSP1 – Steam Flow Transmitter Signal Type
Screen: Steam System
Range: Linear/Square Root
LD09279
Default: 24,000 Lb/Hr
Default: 6000 Gal/Min
Default: 8000 Gal/Min
Default: Linear