Using The 5220 Module; Polarity Reversal Connection Using The 5220 Module - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
compatible rating.

4.17.4.1 Using the 5220 Module

When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current:100 mA, 24 VDC
Alarm:100 mA, 24 VDC
To install the 5220 for polarity reversal, follow the steps below:
1.
Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of
conduit (must not exceed 20 feet in length).
2.
Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure 4-59. This dia-
gram also shows how to connect the 5220 to the remote indicator. Do not install an EOL resistor in the ter-
minals of the Flexput circuit used for this application.
3.
Connect earth ground wire to the 5220 chassis with mounting screw.
4.
Program the Flexput circuit as a notification circuit, refer to Section 9.5.3. Assign this Flexput to an output
group that is mapped to activate with non silenceable constant output in response to a system general alarm
condition.
5.
If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal loop current is 2-
to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm.
Intended for connection to a Polarity Reversal
circuit of a Remote Station receiving unit having
compatible ratings.
Figure 4-59 Polarity Reversal Connection Using the 5220 Module
jumper these terminals
when City Box is not used.
4-43
LS10143-001SK-E
Note:
Flexput circuit 1 and Relay 2
used as examples. Any
Flexput circuit and either
relay 1 or relay 2 could
be used.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents