Manual Alarmnet Registration; Silence Alarms Or Troubles; Reset Alarms; Reset Communicator - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
2.
Select 5 for Communicator Test. The screen will display "Manual communicator test started". When the test
is completed, you will be returned to the <Test Menu>. A manual communicator test requires that at least
one daily test in the network be enabled in communicator programming.
3.
The Manual communicator test will be communicated out both Phone Lines and Ethernet/Cellular paths if
they are all programmed. Each manual communicator test will alternate between one of the Phone Line
paths and one of the AlarmNet paths.
10.4.8

Manual AlarmNet Registration

1.
From the Main Menu, press 1 for System Tests.
2.
Select 8 for Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if
the command was sent or not.
10.4.9

Silence Alarms or Troubles

Press SILENCE to turn off silenceable outputs and annunciator PZTs. If an external silence switch has been
installed, activating the switch will silence alarms or troubles. If you are already using system menus when you
press SILENCE, you will not need to enter your code.
Note: Alarm and trouble signals that have been silenced, but the detector remains un-restored, will un-silence
every 4 or 24 hours depending on user selection (see section
Note: Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the
PZT built into the annunciator. To silence a site, enter a multi-site access password, select a site, and then
press SILENCE.
Note: For ECS systems, pressing silence at an LOC will only silence the System in Control. See Section 10.5.1.

10.4.10 Reset Alarms

Press RESET to perform a control panel reset. If an external reset switch has been installed, activating the switch
will reset fire alarms.
Note: Multi-Site displays do not allow for resetting multiple sites. To reset a site, enter a multi-site access pass-
word, select a site, and then press RESET.
Note: For ECS systems, pressing reset at an LOC will prompt the user for which system they desire to reset. See
Section 10.5.1.

10.4.10.1 Reset Communicator

This options allows the user to Reset the communicator. The LCD will display:
"Resetting Communicator... Please Wait"
You will be returned to the Main Menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not
allowed if any of the following are active:
Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
ECS Alarm
ECS Supervisory
until the detector is restored.
9.6.4.6)
10-6
System Operation