LS10143-001SK-E

6.2.6.4 Communicator Reporting Table

The Communicator Report Table specifies event reporting for each panel on the network. Each row in the table
specifies a panel, event types to report, primary and backup receiver numbers, and report by point or zone.
Associated with the receivers are account number and daily test option. The table can have up to 99 rows.
1.
From the main menu.
2.
Select 6 for Network Programming.
3.
Press 6 to enter Communicator Options menu.
4.
Select 4 for Communicator Reporting Table.
5.
Press * to add rows, Press ENTER to edit data
6.3

Voice Options

6.3.1

Edit Timers

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers

6.3.1.1 Control Lockout

The Control Lockout countdown timer is set to the programmed value when an LOC gains ECS Control. The
timer starts over upon any key press at the ECS Control LOC. While the Control Lockout timer is active, an LOC
of equal priority must request ECS control. The Control Lockout timer is cleared when ECS Control is
relinquished. The Control Lockout timer does not apply to ECS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
Reporting Format
UNUSED
Figure 6-1 Communicator Reporting
6-6
Network Management