Smoke Detector Sensitivity

Drift compensation is automatic for all smoke detectors (photoelectric and ionization). The feature is always in effect, no
programming is required. See Section 10.4.11 for information about how to check if a detector is in UL compliance.
All detectors in the zone will respond as programmed in this menu location.
Detector
Type of Smoke
Protocol
Detector
IDP/SK
Photo, Acclimate, &
Photo-T
DNR with PhotoR
or Photo
SD
SD505-PHOTO
SD505-DUCT with
SD505-DUCTR
SD505-DUCT with
SD505-DUCTR
* Automatic drift compensation is always in effect for all detectors. See Section 10.4.11 for in-
formation about how to check if a detector is in compliance.
4.
Use the up or down arrow key to scroll through the range or enter directly from the number keys on the
annunciator, then press ENTER.
Note: If the SLC protocol is changed from IDP/SK to SD and a zone's sensitivity is higher than the SD limit, the
zone sensitivity will be set to the max value, 150, for the SD family.

9.3.1.3 Zone Accessory Options

1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23 if using IDP or SK. Choose from 00-
16, 23 if using SD devices). See Appendix C.
CO Single and Multistation Cadence (choose from Cadence Patterns 00 to 02, 23 for IDP or SK devices).
Note: The B200S Sounder base provides the recommended CO cadence pattern.
Local Zone (choose Y or N, for Yes or No).
Note: If the SLC protocol is changed from SD to IDP/SK series and the cadence is no longer valid for IDP/SK,
the zone cadence will be set to constant on.
IMPORTANT!
Table 9-2: IDP/SK and SD Sensitivity Choices*
Choices
Low (3.5% obscurity)
Medium (2.5% obscurity)
High (1.5% obscurity)
Low (2.5% obscurity)
Medium (2.0% obscurity)
High (1.5% obscurity)
Low
Medium
High
Fixed
Fixed
9-6
Comments
If the day/night sensitivity option is selected, you can have
different sensitivity settings during the day and at night. You can
program the days of the week that Day/Night Sensitivity will
automatically adjust. You can also designate specific days as
holidays. Holiday and weekend days use night sensitivity for the
entire day.
If the day/night sensitivity option is selected, you can have
different sensitivity settings during the day and at night. You can
program the days of the week that Day/night sensitivity will
automatically adjust. You can also designate specific days as
holidays. Holiday and weekend days use night sensitivity for the
entire day.
Low, Medium and High settings have no effect for photoelectric
duct detectors. Photoelectric duct detector sensitivity is always
1.1% per foot. Day and night settings also have no effect on
these detectors.
Low, Medium, or High settings have no effect for ionization duct
detectors. Ionization duct detector sensitivity is always 75 MIC
(0.8%) regardless of Low, Medium or High setting. Day and night
settings also have no effect on these detectors.