Current Draw Worksheet For Sd Slc Devices - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
Device
1. The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated
by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3.7.4

Current Draw Worksheet for SD SLC Devices

Use Table 3-4 to determine current requirements during alarm/battery standby operation when SD SLC devices
are installed. You can install up to 127 SD devices per loop (2032 max per panel). Copy this section if additional
space is required. 1
Table 3-4: Current Draw Worksheet for SD SLC Devices
Device
For each device use this formula:
Fire Panel (Battery current draw)
SD500-AIM
SD500-MIM
SD500-PS
SD500-ARM
SD505-HEAT
SD505-PHOTO
SD500-ANM
SD500-SDM
SLC Accessory Base
SD505-6RB
SD505-6SB
Table 3-3 Current Draw Worksheet for SK SLC Devices
# of Devices
# of Devices
This column
X
Standby:
1
Alarm:
Standby/Alarm:
Aux. Pwr
SLC
SLC
Aux. Pwr
Standby/Alram:
Aux. Pwr
SLC
Current per Device
Total ampere hours
Current per Device
This column
=
Current per number of devices.
230 mA
415 mA
.55 mA
Standby:
Alarm:
Standby/Alarm:
Standby/Alarm:
Standby:
Alarm:
106 mA
.082 mA
Standby:
Alarm:
Standby/Alarm:
.082 mA
3-15
LS10143-001SK-E
Standby
Alarm
Current
Current
required
Standby
Alarm Current
Current
230 mA
mA
mA
mA
6
mA
mA
mA
8 mA
mA
60 mA
.55 mA
mA
.55 mA
mA
20 mA
mA
mA
1 mA
mA
32 mA
mA
415 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA