Wiring The Widp-Wgi Or Sk-Wgi; Power Connections For The Gateway - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual

7.10 Wiring the WIDP-WGI or SK-WGI

Note: The WIDP-WGI or SK-WGI, as part of the wireless network, has been tested for compliance with the Fed-
eral Communications Commission (FCC) requirements of the United States Government. It has not been
evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to
which this product may not conform. It is the sole responsibility of the user to determine if this product may
be legally used outside the USA.
Note: It is recommended to use the same wire gauge is there are multiple connections to the same terminal.
For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000FH-E or
LS10036-000SK-E.
7.10.1

Power Connections for the Gateway

The WIDP-WGI or SK-WGI, Wireless Gateway acts as a bridge between a group of wireless fire devices and a
SLC loop on the IFP-2100/ECS. It is powered by the SLC loops or by a regulated, external 24 VDC UL listed
power supply. See Table 7-4 for available wireless devices & modules. For details about wireless devices, system
setup, and operation, see the SWIFT
LS10036-000FH-E if using IDP or P/N LS10036-000SKFL-E for SK.
Smart Wireless Integrated Fire Technology Instruction Manual P/N
7-11
LS10143-001SK-E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents