Estimated Runtime On Internal Batteries - Toshiba 5000 SERIES Installation And Operation Manual

Nema-3r 3-phase ups. industrial duty 3-phase ups
Hide thumbs Also See for 5000 SERIES:
Table of Contents

Advertisement

11.5

Estimated Runtime on Internal Batteries

Following are charts of the estimated runtime for the 5000 Series 20kVA on internal batteries at various loads at a 0.8 and
0.9 Power Factor.
These runtimes are estimates based on new batteries operating at 76 °F. Actual runtimes may vary due to manufacturing
variations, previous discharge profiles, battery age, and operating temperature.
TABLE 11.1: ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS – 0.8 PF
UPS
20kVA (0.8 PF)
1 – Subject to change without notice.
TABLE 11.2: ESTIMATED RUNTIME ON INTERNAL BATTERIES AT VARIOUS LOADS – 0.9 PF
UPS
20kVA (0.9 PF)
1 – Subject to change without notice.
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000
Estimated Runtime in Minutes at Percent Full Load
10%
20%
30%
40%
>60
42
28.5
Estimated Runtime in Minutes at Percent Full Load
10%
20%
30%
40%
>60
38
25
50%
60%
70%
25
21.5
19
17
50%
60%
70%
23
20
17.5
14.5
1
1
80%
90%
100%
14.5
13.5
11.5
1
1
80%
90%
100%
13
12.5
10.5