Installation Planning Guide for Industrial Duty UPS
Standard System: 208/120V Input, 208/120V Output
Dimensions
UPS kVA/
Config
kW Rating
Inches (mm)
20/30 kVA/
1-Cab.
59.38 x 38.70 x 92.09
18/27kW
(1508 x 983 x 2340)
20/30 kVA/
2-Cab.
84.34 x 38.72 x 92.09
18/27kW
(2143 x 984 x 2340)
Maximum Input Power Demand
kVA
PF
Amps
20
>0.99
57 (62)
30
>0.99
86 (91)
Maximum Input Power Demand
kVA
PF
Amps
20
>0.99
56
30
>0.99
83
Battery Capacity Required
Maximum Discharge
for Full Load Output
at Full Load Output
kVA
kWB
20
20
30
30
1 - External overcurrent overprotection not needed if battery cabinet(s) are each equipped with an appropriate internal circuit breaker.
2 - External feeder cables may change depending on number of battery cabinets placed in parallel.
Maximum Output Power Demand
kVA
PF
Amps
20
0.9
56
30
0.9
83
92
5000 Series UPS
20/30kVA
GENERAL MECHANICAL INFORMATION
Est. Heat
Weight
Loss
Lbs.
kBTU/Hr
1700
7.6 / 12.6
2680
7.6 / 12.6
PRIMARY AC INPUT (208/120V 3-PHASE / 4-WIRE)
Suggested External
Suggested Minimum Feeder Wire Size per
Feed Breaker
Amps
80 A
110 A
1/0 – 2/0 / 4/0 – 250 kcmil
BYPASS AC INPUT (208/120V 3-PHASE / 4-WIRE)
Suggested External
Suggested Minimum Feeder Wire Size per
Feed Breaker
Amps
80 A
110 A
1/0 – 2/0 / 4/0 – 250 kcmil
BATTERY BACKUP (288 VDC NOMINAL)
Suggested External
Feeder Breaker
Amps
Amps
87 A
90 A
130 A
150 A
AC OUTPUT (208/120V 3-PHASE / 4-WIRE)
Suggested External
Suggested Minimum Feeder Wire Size
Feed Breaker
Amps
80 A
110 A
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000
Mechanical Clearance for Ventilation and Maintenance
Access
Front
Left Side
Right Side
36 in.
6 in.
36 in.
(914 mm)
(152 mm)
(914 mm)
36 in.
6 in.
36 in.
(914 mm)
(152 mm)
(914 mm)
Phase / Neutral
AWG or kcmil a 75 °C Temp. Rating
#3 – #2 / 2/0 – 3/0
Phase / Neutral
AWG or kcmil a 75 °C Temp. Rating
#3 – #2 / 1/0 – 2/0
Suggested Minimum Feeder
Wire Size
1
2
AWG or kcmil a 75 °C Temp. Rating
#4 – #3
#1 – 1/0
per Phase / Neutral
AWG or kcmil a 75 °C Temp. Rating
#3 – #2 / 1/0 – 2/0
1/0 – 2/0 / 4/0 – 250 kcmil
Back
Top
0.0 in.
6 in.
(0.0 mm)
(152 mm)
0.0 in.
6 in.
(0.0 mm)
(152 mm)
Suggested Max. Feeder
Length for Min. Wire Size in
Steel Conduit
Feet
380
380
Suggested Max. Feeder
Length for Min. Wire Size in
Steel Conduit
Feet
380
380
Suggested Max. Feeder
Length for Min. Wire Size
in Steel Conduit
Feet
70
70
Suggested Max. Feeder
Length for Min. Wire Size in
Steel Conduit
Feet
380
380