UPS Anchorage

Anchorage Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 8.3 for anchor bolt installation detail.
Use 5/8 in. (16 mm) diameter anchor bolts. There are 0.63 in. (16 mm) diameter holes provided in the UPS
base. See Figure 8.4 – 8.10 for the hole locations and dimensions for the specified UPS models.
8.4

UPS Anchorage - Single Cabinet

Use 5/8 in. (16 mm) diameter anchor bolts. There are four (4) x 0.63 in. (16 mm) diameter holes provided
in the UPS base. See Figure 8.4 for the hole locations and dimensions in inches (mm) for the specified
UPS model.
Following is the layout for the anchorages and footprint the Single Cabinet 5000 Series UPS.
FIGURE 8.3: 5000 SERIES SINGLE CABINET UPS ANCHORAGE AND FOOTPRINT
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000
5.25
3.0
16
(76)
(406)
(133)
(Bottom) Power
Conduit Landing
Plate
1.25 (31)
12.25
21.0
(311)
(533)
4 x Ø 0.63)
*DIMENSIONS: in. (mm)
37.0
(941)
2.7
(69)
Single
Cabinet
Footprint
27