Transporting By Crane - Toshiba 5000 SERIES Installation And Operation Manual

Nema-3r 3-phase ups. industrial duty 3-phase ups
Hide thumbs Also See for 5000 SERIES:
Table of Contents

Advertisement

4.4

Transporting By Crane

Cables should have sufficient load ratings and be of the same length. Ensure the suspension cables are
hooked at eyebolts. See Figure 4.4.
Use a spreader bar between the Front and rear pair of lifting eye cables as shown below to avoid bending
or damaging the fan exhaust hood(s). Use 30 in. (min.) spreader bars for the single cabinet UPS, and 55
in. (min.) spreader bars for the dual cabinet UPS.
Keep the angle less than 60° between cables. Figure 4.5 and 4.6 show unacceptable lifting practices.
Refer to Appendix A - Weight and Dimension for UPS cabinet.
Keep UPS leveled when lifting. DO NOT swing or tilt the UPS. Minimize the impact when lowering the UPS
to the floor. Figure 4.7 and 4.8 show examples of acceptable and unacceptable operations.
More than 60°
FIGURE 4.5: ANGLE MORE THAN 60°
FIGURE 4.7 ACCEPTABLE OPERATION
10
FIGURE 4.4: CABLES AND EYEBOLTS TO LIFT THE UPS
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000
Less than 60°
Two user-supplied spreader bars:
Single Cabinet: 30 in.
Dual-Cabinet: 55 in.
Uneven Cables
FIGURE 4.6: UNEVEN CABLES
FIGURE 4.8: UNACCEPTABLE OPERATION