Table 1.1 Ups Installation Environment - Toshiba G8000MM Series Installation And Operation Manual

Hide thumbs Also See for G8000MM Series:
Table of Contents

Advertisement

!
NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate
insulation, shorten component life and cause malfunctions.
Keep the installation environment per standard described as follows:

Table 1.1 UPS Installation Environment

No.
Item
1
Installation
Indoors
location
2
Ambient
Minimum temperature: 0 C, Maximum temperature: 40 C The average
temperature
temperature over any 24-hour period must be in the range 5 to 35 C.
3
Relative
The relative humidity must be held between 5 and 95%. There must be no
humidity
condensation due to temperature changes.
4
Altitude
This equipment must not be applied at altitude that exceeds 2700 m (9000 ft.)
above seal level.
5
Dust
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron particles,
oils or fats, or organic materials such as silicone.
6
Inflammable gas There should be no inflammable/explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NO
Ozone (O
Hydrochloric acid mist (HCl)
4
WARNING 3
4
Environment standard
S)
2
)
2
)
2
)
3
)
2
)
x
)
3
G8000MM
No more than 0.0001 PPM
No more than 0.05 PPM
No more than 0.002 PPM
No more than 0.1 PPM
No more than 0.02 PPM
No more than 0.02 PPM
No more than 0.002 PPM
3
No more than 0.1 mg/m
Installation and Operation Manual