Troubleshooting For The Module As00Scm As A Communication; Module - Delta AS Series Operation Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

A S S e r i e s H a r d wa r e M a n u a l
Error
Code
The signal received by channel 1 exceeds
16#1808
the range of analog inputs or the SEN
voltage is abnormal.
The signal received by channel 1 exceeds
16#1809
the weight limit.
The factory calibration in channel 1 is
16#180A
incorrect.
_12
The signal received by channel 2 exceeds
16#180B
the range of analog inputs or the SEN
voltage is abnormal.
The signal received by channel 2 exceeds
16#180C
the weight limit.
The factory calibration in channel 2 is
16#180D
incorrect.

12.3.3 Troubleshooting for the Module AS00SCM as a Communication

Module

12.3.3.1
ERROR LED Indicator Are ON
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
16#1605
Hardware failure
16#1606
The function card setting is incorrect.
12.3.3.2
ERROR LED Indicators Blinking Every 0.5 Seconds
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
16#1802
Incorrect parameters
16#1803
Communication timeout
16#1804
The UD Link setting is incorrect.
The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the
1 2 - 1 6
Description
Description
Description
Solution
Check the signal received by channel 1 and the cable
connections.
Check the value input to channel 1 and the maximum
weight setting.
Check the weight calibration in channel 1.
Check the signal received by channel 2 and the cable
connections.
Check the value input to channel 2 and the maximum
weight setting.
Check the weight calibration in channel 1.
Solution
1.
Check that the module is securely installed.
2.
Install a new AS00SCM or contact the factory.
1.
Check if the function card is securely installed.
2.
Install a new function card or contact the factory.
3.
Check if the setting in HWCONFIG is consistent with
the function card setting.
4.
Install a new AS00SCM or contact the factory.
Solution
Check the parameter in HWCONFIG. Download the
parameter again.
1.
Check whether the communication cable is properly
connected.
2.
Check if the station number and the communication
format are correctly set.
3.
Check if the connection with the function card is
working correctly.
1.
Check the settings of the UD Link.
2.
Check the warning settings in the PLC.