Table of Contents

Advertisement

7 Hydrostatic Test

Hydrostatic Test
Preparing for the hydrostatic test
A pop-off relief valve is recommended on cold water
feed line to prevent over pressurization.
Install return header pipe per instructions on page 13.
Seal the front ports with blank flanges and gaskets.
Install return header or flange on the lower tapping
with gasket provided (Fig. 16).
Install supply header at the top tapping of the rear
section. See Chapter 10, page 20 for details. Install a
temporary air vent (not provided) in one tapping.
Cap off return and supply headers. (Blank flanges,
gaskets or plugs not provided).
Install fill/drain valve at the lower rear connection
(Fig. 16).
Install long shank well into 3/4" tapping of rear section.
Fill the boiler. Vent the boiler at the air vent until water
appears. Close the vent and pressurize the boiler.
The assembled boiler shall be subjected to a hydrostatic
test pressure not less than 1
allowable working pressure. The maximum test pressure
shall not exceed the required test pressure by more
than 10 psi.
If a nipple port connection is leaking, bleed off test
pressure, drain water through the fill/drain valve,
remove the four tie and the return header pipe rods.
Split the boiler at the leaking joint by driving chisels at
the top and bottom between the sections (Fig. 17).
Remove old nipples and clean ports as shown on
page 9. Reinstall flue sealing material. Material can be
reused. Reassemble per instructions on pages 10-12.
NOTE:
reassembling the boiler .
Repeat the hydrostatic test to ensure no leaks.
Install relief valve after the hydrostatic test.
12
times the maximum
1/2
Always use new push nipples when
3/4" tapping
Supply
header
Return
header
Lower rear
connection
Fill and drain
valve (3/4")
Fig. 16
Chisel
Fig. 17
Chisel

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents