Repair Information

If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest Johnson Controls representative.

Technical Specifications

TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability (Part 1 of 2 )
Power Requirements
USB Port Power Rating
Relay Contact
On/Off or
Rating
Floating Control
Fan Relay Output Rating
Auxiliary Output Rating/Triac
Output
Binary Inputs
Analog Inputs
Temperature Sensor Type
Wire Size
MS/TP Network Guidelines
Temperature
Backlit Display
Range
Heating Control
Cooling Control
Accuracy
Temperature
Humidity
Minimum Deadband
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Ambient
Operating
Conditions
Storage
Compliance
BACnet
International
United States
Canada
Europe
Australia and
New Zealand
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
120 to 250 mA current draw supported
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Dry contact across terminal COM to terminals BI1, BI2, or COS
Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN or COS
Local 1k ohm platinum sensor
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
Up to 100 devices maximum for each Network Automation Engine (NAE);
4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical Bulletin for
the Metasys, FX, or Verasys system installed.
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
-22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific
Controller (B-ASC)
UL Listed, File E27734, CCN XAPX, Under UL60730
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
UL Listed, File E27734, CCN XAPX7, Under E60730
Industry Canada, ICES-003
CE Mark – Johnson Controls declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
RCM Mark, Australia/NZ Emissions Compliant