Tec3000 series, on/off or floating fan coil and individual zone thermostat controllers with dehumidification capability
Table of Contents

Advertisement

Table 10: Menus and Submenus (Part 5 of 9)
Level 1
Level 2
(LCD Screen Name)
Control Setup
Cool Process Range*
(Cont)
Cool Saturation Time*
Cool Time Constant*
Cool Process Dead Time*
Cool Period*
Equipment Size
Network Setup
FC Comm Mode
BACnet Instance ID*
N2 Device Address*
BACnet Device Address*
MSTP Baud Rate*
BACnet Encoding Type
BACnet/MSTP Communication Mode
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Level 3
(Default Values)
40°F
600 seconds
720 seconds
72 seconds
60 seconds
Normal
BACnet/MSTP
1
4
4
Auto
ISO 10646
(UCS-2)
Capability Installation Instructions
38
1
Available Values
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
Normal or Oversized
*Value only appears when Temp Control
Setup is not equal to On Off Control
BACnet/MSTP, N2
0 to 4,194,302
* BACnet/MSTP communication mode
1 to 255
* N2 communication mode
4 to 127
* BACnet/MSTP communication mode
Auto, 1200, 9600, 19200, 38400, 76800
* BACnet/MSTP communication mode
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)