The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode.
When the door is open, motion detected by the sensor is ignored. Note that opening the door does not stop an
Occupied period started by the motion sensor prior to opening the door.
The polarity of the inputs are provided in Table 9.
Table 9: Input Polarities
BI Configuration
Occupancy
Temp Occ
Motion NO
Motion NC
Dirty Filter
Service
Fan Lock
Open Door
Open Window
Supply Fan Status
Configurations that support both BIs configured for the same feature of the action that occurs when either of
1.
the BIs enter that state.
Aux Control
The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
seven different options:
•
Not Used—Output is always off
•
Occupied NO—Output is normally open, but closes when occupied
•
Occupied NC—Output is normally closed, but opens when occupied
•
Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
•
Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
•
On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
•
Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Aux Mode and set accordingly.
5. Press
to save and
This option is also exposed to the BAS through the point AUX-MODE.
When the Reheat installed parameter is set to True, the Aux output is used for Reheat Output. The setting for the
Aux Mode is ignored when reheat is enabled.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Contact Open
Unoccupied
No Trigger Active
No Motion Detected, Standby
Motion Detected, Occupied
Dirty Filter Alarm Inactive
Service Alarm Inactive
No Airflow
Door Open, Unoccupied
Window Open, Control Shut Down
Supply Fan Off
to return to the previous screen.
Capability Installation Instructions
Contact Closed
Occupied
Temporary Occupancy Trigger
Motion Detected, Occupied
1
No Motion Detected, Standby
Dirty Filter Alarm
Service Alarm
Airflow
Door Closed, Occupied
Window Closed, Control Running
Supply Fan On