Johnson Controls TEC3310 Installation Instructions Manual page 18

Tec3000 series, on/off or floating fan coil and individual zone thermostat controllers with dehumidification capability
Table of Contents

Advertisement

6. Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive's root directory.
See Troubleshooting if the settings are not backed up correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive's root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Choosing the Communication Mode
TEC3613-00-000 Models)
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Network Setup.
4. Press FC Comm Mode.
5. Select BACnet or N2 by pressing
6. Proceed to Step 7 to perform BACnet communication and Step 15 to perform N2 communication.
7. Press
to return to the previous screen.
8. Press BACnet Instance ID.
9. Enter the unique BACnet® instance ID using the keypad. This value should be different to the other controllers
on the site.
10. Press Save.
11. Press
to return to the previous screen.
12. Press BACnet Address.
13. Enter the BACnet MS/TP address through the keypad.
14. Press Save.
15. After selecting N2 in Step 5, press Save.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
(TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, and
.
Capability Installation Instructions
18

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tec3320Tec3321Tec3322Tec3312Tec3311Tec3330 ... Show all

Table of Contents