Johnson Controls TEC3310 Installation Instructions Manual page 39

Tec3000 series, on/off or floating fan coil and individual zone thermostat controllers with dehumidification capability
Table of Contents

Advertisement

Table 10: Menus and Submenus (Part 6 of 9)
Level 1
Level 2
(LCD Screen Name)
Equipment Setup
General
Unit Type
Heating/Cooling Device Type*
Actuator Stroke Time*
Cooling Min On Time*
Cooling Min Off Time*
Heating Min On Time*
Heating Min Off Time*
Unoccupied Off Delay
Supply Fan
Supply Fan Type*
Start Voltage*
Full Speed Voltage*
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Level 3
(Default Values)
4-Pipe
Floating
30 seconds
120 seconds
120 seconds
120 seconds
120 seconds
10 minutes
Single-Speed
2 VDC
10 VDC
Capability Installation Instructions
39
1
Available Values
2-Pipe, 4-Pipe, VAV
On/Off, Floating
* Fan coil units only
5 to 300
* Floating Heating/Cooling device type
only
0 to 360 seconds
* Fan coil on/off units only
0 to 360 seconds
* Fan coil on/off units only
0 to 360 seconds
* Fan coil on/off units only
0 to 360 seconds
* Fan coil on/off units only
0 to 10 minutes
Single-Speed, Multi-Speed,
Variable-Speed
* Fan coil units only
0 to 10 VDC
* Fan coil units only, variable-speed fan
0 to 10 VDC, proportional
*Fan coil units only, variable-speed fan