General Requirements - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Emergency operation
4.5

General requirements

4.6
Wiring principle
E3X10. (CPU)
Terminal block X16
A2/B2
A1/B1
Supply circuit 2
(Emergency supply)
Supply circuit 1
Emergency operation circuit
C-Bus
C-Bus return line, Note 1
Note 1 C-Bus loop line = max. 1000 m (at G51 Ø0.6mm) incl. return line or, max. 1400 m at G51 Ø0.8 mm
Application
24V supply from control unit
Complies with EN54
24V supply from control unit
without emergency operation / emer-
gency power supply
autonomous power supply
Complies with EN54
autonomous power supply
without emergency operation / emer-
gency power supply
Note:
Emergency operation circuit also required between other CPUs or to a separate Gateway
Emergency operation circuit and the emergency power supply are not laid out as a loop line
Route emergency power supply in a separate cable or in the C-Bus cable feedback
22
Building Technologies
Fire Safety & Security Products
At least one control console per system must comply with standard EN54, i.e.
must have Emergency operation capability and Emergency power supply.
Emergency power supply
This consists of a second supply circuit to stations located elsewhere
For this purpose the AlgoPilot control console has 2 de-coupled supply inputs
AlgoPilot B3Q...
K5
K7
K6
A2/B2
A1/B1
Two requirements must be met for control consoles located elsewhere. At least
one control console must comply with standard EN54 (i.e. have emergency opera-
tion capability and emergency supply).
EN54 requirements:
Communication as loop line
Operation also in emergency mode
second de-coupled 24 V supply
The number of wires in the connection cable depends on the application:
a) Are control consoles supplied from the control unit or autonomously with 24V?
b) Is an emergency power supply also provided according to EN54?
c) Is the emergency operation circuit also provided?
C-Bus
24 V supply
X (2 wires)
X (3 wires)
X (2 wires)
X (3 wires)
X (2 wires)
X (2 wires)
AlgoPilot B3Q...
K5
K7
K6
A2/B2
A1/B1
(=C-Bus designed as loop line)
(=3 additional wires for emergency
operation between CPU and control consoles)
(=3 additional wires if there is no
autonomous power supply)
Emergency
supply
X (2 wires)
AlgoPilot B3Q...
K5
K7
K6
A2/B2
Emergency op-
Number of wires
eration circuit
X (3 wires)
10
5
X (3 wires)
5
2
001260_k_en_--.doc
A1/B1
02.2005