E3X102/103 Master module (supersedes E3X101)
54
Building Technologies
Fire Safety & Security Products
LED "Battery fault
c) Operation with
LED "Power supply fault
external voltage (in-
stead of battery)
LED "Power on"
LED "Battery fault
d) Operation without
LED "Power supply fault
battery or external
voltage
LED "Power on"
LED "Battery fault
18
Programming switch "S3": Choice of "I-Bus address battery charger"
To set I-Bus address for the Function unit "Charge /monitor battery". This unit is
an I-Bus user (as e.g. line module) and must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices
Function / I-Bus address
No.
0
Module out of commission (unused)
1
I-Bus user number
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
Battery voltage < 23 V
Open line to battery or fuse F501 / F502 blown
Autom. test to indicate battery presence negative
Autom. battery load test negative
Input voltage > 31.0 V –> power unit malfunction
EEPROM check sum error
Input voltage > 28.5 V
Battery voltage or external voltage < 23 V or > 31.0 V
Autom. presence test (external voltage) negative or fuse F501 / F502
blown
Input voltage > 31.0 V –> power unit malfunction
EEPROM check sum error
Input voltage > 28.5 V
no function
S3-1
off
1
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
Programming switch S3
S3-2
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on