E3X100 Master module (superseded by E3X101)
E3X100
Supply neutral point,
20...30V
(not protected by fuse)
Input voltage,
29,6V 2%
0V (not fuse-protected)
Supply for
remote transmission
Auxiliary supply
Battery 24V
max. 42Ah,
symmetry monitored
Temperature sensor
for battery
Inputs power supply
FAULT
(default = not active)
Supply for
I-Bus modules
Plug-in terminals
Remote alarm
Double flat cable header
Data communication
I-Bus modules
Flat cable header (Mini)
Data communication RS232
1) PTC is always required including for operation "with external voltage" or "without battery".
2) Function "24V external voltage" or function "without battery" is programmable via maintenance PC. With the function "External voltage"
the battery presence monitoring can be programmed as "active" (i.e. the external voltage is monitored).
3) Valid from EP7F the outputs X17-8, 9, 10, 11 are always monitored. Up to EP5 these outputs can be programmed as monitored.
36
Building Technologies
Fire Safety & Security Products
X17
Terminal block
+
1
+
2
+
3
+
4
-
5
-
6
-
7
+
8
F26
24V/max. 2A
-
9
F27
+
10
24V/max. 2A
-
11
F501
+
12
F503
13
-
14
F502
15
16
17
Emerg. power
Power supply
18
Battery
19
20
C
K1
Plug-in terminals
-
1
1
GND
-
2
+
3
5V
24V
+
4
K2
switch off
1
1
reset
2
3
blocked
4
malfunction
5
6
C
ST1
ST2
from converter B2F020
to remote transmission equipment
to other
internal
red
12V
green
12V
blue
white
PTC
brown
monitors other power sup
ply (internal only)
blue
blue
to the I-Bus modules
green
red
to remote transmission equipment
white
(using cable set Z3I390)
brown
to the I-Bus modules
According to application
- RS232 module (E3I020)
- Printer B2Q191
- Maintenance PC (B3D021)
- PSA/Pager interface K3I090
3)
users
Battery (internal)
or
24V external voltage
1)
2)
001260_k_en_--.doc