Building Technologies
Fire Safety & Security Products
LED "Battery fault
d) Operation without
LED "Power supply fault
battery or external
voltage
LED "Power on"
LED "Battery fault
19
Programming switch "S3": Choice of "I-Bus address battery charger"
To set I-Bus address for the Function unit "Charge /monitor battery". This unit is
an I–Bus user (as e.g. line module) and must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices
Function / I-Bus address
No.
0
Module out of commission (unused)
1
I-Bus user number
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
20
Programming switch "S2": Choice of "battery type"
To set temperature compensation according to information from the various battery
manufacturers
Possible battery variants
Var.
Battery manufacturer
0
1
2
Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
3
Genesis
4
Sunrise
Panasonic
5
Phoenix (Korea)
6
Yuasa
7
Sonnenschein Dryfit
8
Power–Sonic
9
Hagen Drysafe
10
Sonnenschein Dryfit
11
ALARMCOM (FIAMM) 1)
12
13
14
15
"S2" is set to variant 11 (ALARMCOM) at the factory
1) available from index 'AA' onwards
E3X101 Master module (superseded by E3X102/103)
Battery voltage or external voltage < 23 V or > 31.0 V
Autom. presence test (external voltage) negative or fuse F501 / F502
blown
Input voltage > 31.0 V –> power unit malfunction
EEPROM check sum error
Input voltage > 28.5 V
no function
S3-1
off
1
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
Battery model
CF 12-24 (VM 1224)
HP..-12
HP..-12
G12V120W15
LCL 12V24S
LCL 12V..P
FNC 12..0
NP..–12B
A212/..G5
PS12..0
HDS–12..0NB
A512/..G5
FG...
Programming switch S3
S3-2
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
Programming switch S2
S2-1
S2-2
S2-3
off
off
off
on
off
off
off
on
off
on
on
off
off
off
on
on
off
on
off
on
on
on
on
on
off
off
off
on
off
off
off
on
off
on
on
off
off
off
on
on
off
on
off
on
on
on
on
on
001260_k_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
S2-4
off
off
off
off
off
off
off
off
on
on
on
on
on
on
on
on