36

E3G070 Control module "universal"

36.1
Overview
36.2
Key data
36.3
Important components
Building Technologies
Fire Safety & Security Products
Universal control module for smaller systems (instead of E3X10.)
2 contacts for remote transmission "Alarm and fault"
2 monitored control lines for alarm devices with EMI and over voltage protection
7 programmable control outputs / inputs
Monitored supply output for internal devices
Integrated ground fault monitoring
Card format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
"Remote transmission" contacts
"Alarm horn line"
Inputs
Supply output
Terminal block X1 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
1
2
3
4
ASIC
I-BUS
ST1
5
S2
F1
ON
1
6
K1
7
4
E3G070 Control module "universal"
max. load
24 W (60 V, 1 A),
type
choice of make / break contact
max. load 2 A (24 V), with EMI protection
max. load
40 mA (24 V), internal only
activation
via volt-free contact
max. load 630 mA (24 V), internal only
Y13
F6
F7
X13
F8
X60
F9
F2
F3
F4
1
ON
K2
S3
F5
8
H1
X12
Y12
H11
1
10
6
9
001260_k_en_--.doc