Siemens Cerberus CS1140 Manual page 66

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3C011 Battery charging module (supersedes E3C010)
66
Building Technologies
Fire Safety & Security Products
3
Programming switch "S2": Set battery type
To set temperature compensation according to information from the various battery
manufacturers.
Possible battery variants
Var.
Battery manufacturer
0
1
2
Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
3
Genesis
4
Sunrise
Panasonic
5
Phoenix (Korea)
6
Yuasa
7
Sonnenschein Dryfit
8
Power–Sonic
9
Hagen Drysafe
10
Sonnenschein Dryfit
11
ALARMCOM (FIAMM) 1)
12
13
14
15
"S2" is set to variant 11 (ALARMCOM) at the factory
1) available from index '-A' onwards
Floating charge voltage as a function of temperature, or for diagrams of the vari-
ous types of battery see page 44
4
Flat cable header "ST1" (26-pin): I-Bus
5
LED indicator block "Power supply status"
yellow
green
H501
yellow
H502
yellow
Indicators vary in meaning according to application:
a) Battery operation
LED "Power supply fault
and symmetry moni-
toring
LED "Power on"
LED "Battery fault
b) Battery operation
LED "Power supply fault
without symmetry
monitoring
LED "Power on"
Battery model
CF 12-24 (VM 1224)
HP..-12
HP..-12
G12V120W15
LCL 12V24S
LCL 12V..P
FNC 12..0
NP..–12B
A212/..G5
PS12..0
HDS–12..0NB
A512/..G5
FG...
"Power supply fault"
"Mains operation"
"Battery fault"
unused
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5 V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
Input voltage > 28.5 V
Battery voltage < 23 V
Asymmetry > 1.0 V or fuse F503 blown
Possibly cell short circuit
Open line to battery or fuse F501 / F502 blown
Autom. test to indicate battery presence negative
Autom. battery load test negative
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
Input voltage > 28.5 V
Programming switch S2
S2-1
S2-2
S2-3
off
off
off
on
off
off
off
on
off
on
on
off
off
off
on
on
off
on
off
on
on
on
on
on
off
off
off
on
off
off
off
on
off
on
on
off
off
off
on
on
off
on
off
on
on
on
on
on
001260_k_en_--.doc
02.2005
S2-4
off
off
off
off
off
off
off
off
on
on
on
on
on
on
on
on

Hide quick links: