B2Q191 Logging printer
246
Building Technologies
Fire Safety & Security Products
Set baud rate 9600, default value in the CS1140 (AlgoWorks)
Function
Baud rate
300
1200
2400
9600
Baud rate
19200
2
Programming switch "S1": Setting –> character set
Setting character set 'ISO Latin 1'
ISO Latin 1 supports the languages: English, German, Italian, Spanish, Portuguese, Danish, Fin-
nish, Swedish, Norwegian, Dutch and Flemish
Function
Character set
ISO Latin 1
ISO Latin 2
ISO Latin 3 *
ISO Latin 4 *
ISO Latin 5
ISO Greek
ISO Arabic
ISO Hebrew
Character set
ISO Cyrillic
* ISO Latin 3 and ISO Latin 4 are not supported by the control unit
Character set ISO –> generates the following (permanent) communication parameters:
1 start bit
8 data bits
no parity
1 stop bit
3
Link "X11 + "X12": Connection "K3" , or "A1"/"A3" and "A2" active
Header (Micro) «A3»
(HCMOS) is active if:
jumpers "X11" and "X12"
are inserted in connectors
1-2 and the jumpers
"X13" and "X14" are
inserted in connectors 1-2
Interface «K3» (RS232 /
V28) is active if:
links "X11" und "X12" are
inserted in connectors 2-
3, "X13" and "X14" are
not relevant
4
Ribbon header "A1" (14-pin): 0-modem connection –> no function for CS1140
5
Ribbon header "A2" (14-pin): TTL port for modem card K1D... or 3
dem (V28,FSK,PSK)
6
Link "X13 + "X14": Connection "A3" port 2 or "A3", port 3 active
7
Ribbon header "A3" (20-pin, micro): 0-modem connection for internal housing
connection to AlgoPilot
8
Plug-in terminals "K3": Connection RS232 / V28
9
LED indicator block "State printer"
H2
H1
1
green
yellow
2
green
yellow
Programming switch S1
S1-1
S1-2
S1-3
closed
closed
closed
open
closed
closed
closed
open
closed
open
open
closed
closed
closed
open
Programming switch S1
S1-1
S1-2
S1-3
A3
X14
K3
X13
A2
X12
X11
Main program in operation
Motor blocked
Printing on/off
Paper end
S1-4
S1-5
S1-6
S1-7
S1-4
S1-5
S1-6
S1-7
A1
Header «A2» (TTL)
is active if:
links "X11" und "X12"
are inserted in con-
nectors 1-2, "X13"
and "X14" are not
relevant
rd
party mo-
001260_k_en_--.doc
S1-8
S1-8