33.3
Important components
Building Technologies
Fire Safety & Security Products
1
2
1
ASIC
I-BUS
S3
ST1
3
S2
F1
ON
4
1
K1
4
Legend:
1
Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address
Nr.
0
Module out of commission (unused)
1
I-Bus user number 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
"S3-1...6" are set to "off" at the factory
2
Flat cable header "ST1" (26-pin): I-Bus
3
Maintenance switch "S2": To switch on maintenance LEDs for test purposes.
In addition to the relay output, it also enables activation of the corresponding
LED (H1...H8)
S2-on = LED (H1..H8) lights if output is activated.
4
Plug-in terminals "K1": Supply for "I-Bus" modules
5
Fuse: 'F1'
0.5 A/T Module supply
6
Test LEDs 'H1...H8' at rear. Allocation of the individual LEDs –> see page 138
ON
5
S3-1
S3-2
off
on
2
off
3
on
4
off
5
on
6
off
7
on
8
off
9
on
10
off
11
on
12
off
13
on
14
off
15
on
16
off
E3G050 Control module "Contacts"
H1
H8
6
Programming switch S3
S3-3
S3-4
S3-5
off
off
off
off
off
off
off
off
on
off
off
off
on
off
off
off
off
on
off
off
off
on
off
off
on
on
off
off
on
on
off
off
off
off
on
off
off
off
on
off
on
off
on
off
on
off
on
off
off
on
on
off
off
on
on
off
on
on
on
off
on
on
on
off
off
off
off
on
001260_k_en_--.doc
S3-6
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
137
02.2005