Using The Contact Signal Functions; Contact Signal Functions; Type Of Output Signals; Type Of Input Signals - Omron BU100RS Instruction Manual

Uninterruptible power supply
Table of Contents

Advertisement

6 Contact signal functions

6-1 Contact signal functions

6 Using the contact signal functions

6-1 Contact signal functions
Contact Signal
You can develop your unique system based on the following specifications to automate the
process at a power failure. You can perform power-failure processing by allowing the
system to detect the backup signal and also perform system shutdown processing by
allowing the system to detect the Low battery level signal. Also, by inputting the backup
stop signal from the system, you can stop the UPS with a sufficient battery level to prepare
for the next occurrence of a power failure.

6-1-1 Type of Output signals

The UPS has 4 kinds of output signals.
The output circuit consists of an open collector circuit using a photo coupler (a kind of
electronic switch).
Backup Signal output (BU)
Low battery level signal output (BL)
Trouble Signal output (TR)
Battery Replacement Signal output (WB)

6-1-2 Type of Input signals

The UPS has 2 kinds of input signals.
Input of the UPS Stop Signal (BS)
Remote ON/OFF Signal
Note 1: BS Delay Time:
You can set the amount of time between when the BS signal is received and when the output of
the UPS is stopped (See also "3-5-2 Settings").
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10
seconds from the outside.
Note 2: Connection terminals are at contact signal port pins 6, 7 and the remote ON/OFF port (See
also "3-1-4 Setting Switch").
80
Signals
Stays ON during backup operation at a power failure.
Goes ON when the battery becomes weak during backup operation
at a power failure.
Goes ON when an internal failure of the UPS occurs or when the
battery life counter expires.
Goes ON when the test determines that battery replacement is
necessary due to deterioration or when the battery life counter goes
off-scale.
Signals
When the BS signal is ON (High), the output of the UPS is stopped
after the time period specified in advance has elapsed. (Note 1).
Remote ON/OFF signals can be used to start and stop the UPS, by
using either an externally connected contact or the ON/OFF status
of the open collector circuit.
When signal is OFF, the UPS will be turned on. When signal is ON,
the UPS will be turned off.
In the factory settings, the UPS stops operation when this is
short-circuited.
In addition, it is necessary to turn on the "Power" switch of UPS to
use this function (Note 2).
Descriptions
Descriptions
BU100RS

Advertisement

Table of Contents
loading

Table of Contents