4.
Ensure that the screws are tightened.
As shown in the figure below, check that there is no gap between the rack and each ear
bracket.
If a gap exists, as in step 3, while lifting the rear side, make the UPS level and tighten
the screws again to eliminate the gap.
* Proceed to step 5 if there has been no problem so far.
5.
Periodically check that the screws are not loose and that there is no gap between metal
sheets.
If a gap exists, while holding the whole UPS, tighten the screws again with the specified
tightening torque (2.75±0.2N・m).
Note: A loose screw may cause damage to the product.
Then, the installation process is completed.
BU100RS
Correct installation
No gap
2 Installation and connection
2-1 Installation
Incorrect installation
Gap
2
29