Omron BU100RS Instruction Manual page 30

Uninterruptible power supply
Table of Contents

Advertisement

4.
Ensure that the screws are tightened.
As shown in the figure below, check that there is no gap between the rack and each ear
bracket.
If a gap exists, as in step 3, while lifting the rear side, make the UPS level and tighten
the screws again to eliminate the gap.
* Proceed to step 5 if there has been no problem so far.
5.
Periodically check that the screws are not loose and that there is no gap between metal
sheets.
If a gap exists, while holding the whole UPS, tighten the screws again with the specified
tightening torque (2.75±0.2N・m).
Note: A loose screw may cause damage to the product.
Then, the installation process is completed.
BU100RS
Correct installation
No gap
2 Installation and connection
2-1 Installation
Incorrect installation
Gap
2
29