Continued from page 11.
A direct vent terminal may not be recessed into a wall
or siding.
Install a Vinyl Siding Standoff (M&G Dura-Vent #950)
between the vent termination and an exterior wall
covered by vinyl siding material to prevent potential
heat damage to the siding.
SNORKEL TERMINATION:
• HORIZONTAL RUN MUST NOT EXCEED 2 FEET (61 CM).
A 14" (356mm) or 36" (914mm) snorkel termination is
approved in conformance with the vent rise/run and
termination clearance specifications published in this
manual. See figs. 6.8 – 6.9.
The snorkel termination must comply with grade and
building clearance requirements per local and national
building codes.
RE-INSTALL THE TOP PLATE BEFORE
CONNECTING VENT TO THE STOVE.
Min.
12”
30.5 cm
35 1/2”
90.2 cm
Figure 6.8. 14" Snorkel termination.
 14" SNORKEL WILL REQUIRE 12 " VENT OFF STOVE TO MEET
MINIMUM RISE REQUIREMENT
 2 FT. MAX. HORIZONTAL RUN (A) TO SNORKEL TERMINATION
12
C L
14”
36 cm
C L
A
Min.
61 1/2”
156.2 cm
Min.
47 1/2”
115.6 cm
2”
Alcove Depth
2”
51mm
69”
175.3 cm
67”
170.2 cm
35 1/2”
902 mm
Figure 6.7. Minimum vent required for horizontal termination.
 Any horizontally terminated vent run must include a minimum
2 ft. (61 cm) vertical rise.
 At minimum vertical run, the total horizontal run (A) must not
exceed 5 ft. (152.4 cm).
Max. Mantle Depth
2 1/2”
64 mm
Min. Mantle
Clearance
46 3/4”
118.7 cm
35 1/2”
90.2 cm
Figure 6.9. 36" Snorkel termination and mantle clearance.
 2 FT. MAX. HORIZONTAL RUN (A) TO SNORKEL TERMINATION
Max.
24”
61cm
2”
63 7/8”
162.2 cm
36”
91.4 cm
24”
77 1/8”
61cm
195.9 cm
C L
A
41 1/8”
2”
104.4 cm
C L
C L