Main Circuit Terminal And Motor Wiring - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

n
Three-Phase 600 V Class
Table 3.2 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Model CIMR-Ao
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0003
–, +1, +2
5A0004
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0006
–, +1, +2
5A0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
5A0011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
5A0017
5A0022
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
5A0027
5A0032
B1, B2
<1> Gauges listed in
Table 3.2
u

Main Circuit Terminal and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage
to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious
injury by fire as a result of drive damage from line voltage application to output terminals.
n
Cable Length Between Drive and Motor
Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is too
long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long
motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current
may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to
configuration, reduce the ground currents.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Recomm. Gauge AWG,
Terminal
kcmil
are for use in the United States.
Table
Refer to C6-02: Carrier Frequency Selection on page
Applicable Gauge
<1>
AWG, kcmil
14
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
10
10 to 6
10
10 to 6
12 to 6
12 to 10
10
12 to 10
6
8 to 6
8
8 to 6
6
10 to 8
6
10 to 6
6
6 to 4
6
6 to 4
6 to 4
10 to 8
6
8 to 6
3.3. If the motor wiring distance exceeds 100 m because of the system
3.8 Main Circuit Wiring
Tightening Torque
Size
<1>
N·m (lb.in.)
1.2 to 1.5
M4
1.2 to 1.5
M4
1.2 to 1.5
M4
M5
M5
M6
M6
M5
M6
167.
(10.6 to
13.3)
(10.6 to
13.3)
(10.6 to
13.3)
2 to 2.5
(17.7 to
22.1)
2 to 2.5
(17.7 to
22.1)
4 to 6
(35.4 to
53.1)
2 to 2.5
(17.7 to
22.1)
4 to 6
(35.4 to
53.1)
3
59