Allowable Vertical Terminations - Regency P40-LP Owners & Installation Manual

Regency gas fireplace owners and installation manual
Table of Contents

Advertisement

The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90
o
elbows, with Rigid Pipe
Venting Systems for Propane and Natural Gas.
Two 45
elbows equal to one 90
o
o
of four 45
elbows allowed.
o
Vent must be supported at offsets.
Firestops are required at each fl oor level and
whenever passing through a wall.
Maintain clearances to combustibles as listed
in the "Clearances" section.
Refer to "Vent Restrictor Position" section for
details on how to change the vent restrictor
to Set 1 or Set 2 if required.
Note: Must use optional fl ue adapter when using
Rigid Pipe (Part # 770-994).
Regency
®
P40-1 Direct Vent Gas Fireplace
VENTING ARRANGEMENTS

ALLOWABLE VERTICAL TERMINATIONS

elbow. Maximum
2
4
0
40
38
36
34
32
30
28
Vent Restrictor on Set 2
26
24
22
20
18
16
Vent Restrictor on Set 1
14
12
10
8
6
4
2
0
Max. 10' (3m)(centerline to centerline)
Minimum 12" (305mm)
INSTALLATION
8
14
6
10
12 12
Vent Restrictor
Factory Set
18
16
20
21