Gas Connection Inset Gas Connection Width Important: Framing height requires consideration of the hearth depth. Dimension H = H + the thickness of installed hearth. June 2007 Regency Product Specifi cations Book P40-LP1 Propane 12” W.C. (3.00 kPa) 10” W.C. (2.49 kPa) 3.6”...
#946-618 6 Feet #946-616 10 Feet Notes: Liner sections should be continuous without any joints or seams. Only Flex pipe purchased from Regency may be used for Flex installations. Header Horizontal sections must be supported every 3 feet. Non-Combustible Facing Standoff 5”...
Alternate Snorkel Termination Cap Part #1282 (14”) Part #1281 (36”) Minimum 12” (305mm) Vent Restrictor on Set 2 Vent Restrictor on Set 1 Vent Restrictor Factory Set Max. 10’ (3m)(centerline to centerline) June 2007 Regency Product Specifi cations Book 12 12...
3x then the vent restrictor 5’ Min. 6’ Max. 8’ Min. must be set to 1. 6’ Min. 7’ Max. 9’ Min. 7’ Min. 8’ Max. 10’ Min. June 2007 Regency Product Specifi cations Book P40 Gas Fireplace...
Vent Restrictor on Set 2 Vent Restrictor on Set 1 45-3/8” (1143mm) Minimum Please refer to Page 11 (Exterior Vent Terminations) Height Requirement for additional guidelines on vent locations. Vent Restrictor Factory Set June 2007 Regency Product Specifi cations Book...
11’ Min. 8’ Max. 7’ Min. 6’ Max. 12’ Min. 9’ Max. June 2007 Regency Product Specifi cations Book Maximum total pipe: length, of all sections, must not exceed 30 feet. Total horizontal sections must not exceed 9 feet. Minimum of 1’ pipe section between any elbows.