Emerson Rosemount 5408 Reference Manual page 99

Level transmitters non-contacting radar
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Table 7-2:
Configuration Error Details
Host diagnostic message
Factory Calibration Error
Analog Out Span Configura-
tion Error
Analog Out Calibration Error
SIS Multidrop Error
Engineering Unit Configura-
tion Error
Burst Mode Configuration Er-
ror
Start Code Configuration Er-
ror
Table 7-3:
Status - Function Check
LCD display
Host diagnostic mes-
message
sage
SAFE
Safety Mode Not Activa-
ted
DISBLD
Rosemount 5408 and 5408:SIS Level Transmitters
(continued)
Description
The factory calibration in the device is
missing.
The span for the configured analog out
range is too small.
Analog output calibration failed.
HART multidrop mode is not supported for
safety (SIS) devices. Only 4-20 mA output
is supported for safety devices.
One of the configured engineering units is
not supported by the device.
The burst mode configuration is incorrect.
The start code to enable options in the de-
vice is invalid.
Note
Start codes are unique for individual devi-
ces and cannot be copied from one device
to another.
Description
Safety Mode is disabled and device
is in alarm mode.
This device is configured for use in
Safety Instrumented Systems (SIS)
which requires Safety Mode to be
enabled.
Service and Troubleshooting
Recommended actions
Replace the device.
Increase analog out span by adjusting
Upper or Lower Range Value.
1. Try calibrating the analog output
again.
2. If the condition persists, replace the
device.
1. Disable multidrop mode.
2. Change Operational Mode to Control/
Monitoring if device is not intended to
be used as safety device.
3. If the condition persists, restore default
settings and reconfigure device.
1. Check unit configuration.
2. If condition persists, restore default
settings and reconfigure device.
1. Check configuration of burst mode.
2. If condition persists, restore default
settings and reconfigure device.
1. Enter a valid start code for this device
using the Upgrade function.
2. If condition persists, contact your local
Emerson representative to get a valid
start code.
Recommended actions
1. Change Safety Mode to Enabled
for use in SIS application.
2. Change Operational Mode to
Control/Monitoring if device is
not intended to be used as safe-
ty device.
89