Service and Troubleshooting
Table 7-2:
Configuration Error Details
Host diagnostic message
Primary Variable Configura-
tion Error
Measurement Correction
Configuration Error
Threshold Configuration Er-
ror
Factory Approval Error
SIS Configuration Error
Function Not Supported
Antenna Type Configuration
Error
88
(continued)
Description
The Primary Variable selection is not sup-
ported.
Note
Rosemount 5408:SIS only supports level or
distance as Primary Variable.
The factory measurement correction data
is invalid.
The surface threshold configuration is in-
correct.
The Sensor Module factory approval is
missing.
The Transmitter factory approval is miss-
ing.
It is currently not possible to enable Safety
Mode due to other active alerts.
Note
Rosemount 5408:SIS only supports liquids
level measurement when operating in
Safety (SIS) mode.
Functionality in the device is enabled, but
not supported by this device.
Additional features may be enabled by pur-
chasing an upgrade of the device.
The configured Antenna Type is not sup-
ported by the device.
Recommended actions
1. Change Primary Variable to variable
supported by device.
2. Consider purchasing an upgrade of the
device to access additional variables.
1. Restore default settings and reconfig-
ure the device.
2. If the condition persists, replace the
device.
1. In the threshold table, check that dis-
tance-threshold values are entered in
increasing order.
2. Check that the number of threshold
points to use is correct.
3. If condition persists, restore default
settings and reconfigure the device.
1. Restart the device.
2. Restore default settings and reconfig-
ure device.
3. If the condition persists, replace the
device.
1. Clear other active alerts by priority or-
der until this alert is cleared.
2. Change Operational Mode to Control/
Monitoring if device is not intended to
be used as safety device.
3. If the condition persists, restore default
settings and reconfigure device.
1. Check that selections for variables (e.g.
Primary Variable) are supported by this
device.
2. Turn off functionality not supported by
this device.
3. Consider purchasing an upgrade of the
device to access additional variables
and functionality.
4. If condition persists, restore default
settings and reconfigure device.
1. Check configuration of Antenna Type.
2. Make sure the configured antenna type
matches the physical antenna for the
device.