Emerson Rosemount 5408 Reference Manual page 97

Level transmitters non-contacting radar
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Table 7-1:
Status - Failed
LCD display
Host diagnostic mes-
message
sage
MEAS
Level Measurement Lost No valid level reading. Reasons may
FAILUR
CONFG ERROR
Configuration Error
Table 7-2:
Configuration Error Details
Host diagnostic message
Volume Configuration Error
Scaled Variable Configura-
tion Error
Geometry Configuration Er-
ror
Rosemount 5408 and 5408:SIS Level Transmitters
(continued)
Description
be multiple:
No valid surface echo peak in
the measuring range.
Incorrect device configuration.
The device has detected a configu-
ration error. Reasons may be multi-
ple (see
Table 7-2
Description
The volume cannot be calculated correctly
with the current configuration.
The Scaled Variable configuration is incor-
rect.
The configured tank geometry results in a
too large level measuring range for this de-
vice.
Recommended actions
1. Analyze the Echo Curve at time
of loss for reason and check de-
vice configuration, especially
thresholds.
2. Check device physical installa-
tion (for instance antenna con-
tamination).
3. Consider increasing Measure-
ment Recovery Time parameter
for intermittent conditions.
4. Restart the device.
5. Restore default settings and re-
configure the device.
6. If the condition persists, replace
the device.
1. Click the Details button for
more information.
for details).
2. Correct the parameter causing
the error.
Recommended actions
1. If strapping table is used, check that
level-volume values are entered in in-
creasing order.
2. If strapping table is used, check that
number of strapping points to use is
correct.
3. If tank dimensions are used for volume,
check that geometry shape and size
measures are correct.
4. If condition persists, restore default
settings and reconfigure the device.
1. Check that the value pairs in the scaled
variable table are entered in increasing
order.
2. Check the number of table points to
use is correct.
3. If condition persists, restore default
settings, and reconfigure the device.
1. Check tank geometry configuration
and reduce Reference Height.
2. If condition persists, restore default
settings and reconfigure the device.
Service and Troubleshooting
87